|
|
| Figure 2. The isolation
bypass ATS provides functionality useful for maintaining the equipment while
retaining power reliability. |
|
Position 1 is the test
position. In this position, the main power poles of the automatic power
switching device are disconnected; however, control power is still available so
that the ATS may be tested by qualified maintenance personnel equipped with
appropriate personal protective equipment in accordance with the hazard level
identified as defined by NFPA 70E.
Position 2 is the isolate position. In this position the ATS mechanism is
completely disconnected from all power and may be completely removed for
invasive maintenance and repair.
Some things to consider:
- Most manufacturers provide a variety of accessories to fine tune the device to
the application.
- The power transfer switch must be coordinated with other system components, no
matter what type you use. For example, the speed of the transfer may present a
problem for a UPS, variable-frequency drive, or other downstream load. In this
case a pre-signal from the ATS may be desirable. This may be a contact closure
or opening prior to the actual transfer allowing for a connected device to
revert to a controlled state or shut down prior to the transfer. Following
transfer, the action is reversed and all system components return to normal
operation. you may wish to force a UPS to its battery until the transfer is
complete.
- The coordination of setpoints in the system can be a major issue. Take the voltage
drop out or lowest acceptable value for example. Consider what would happen if
the ATS had a lower drop out value programmed into the ATS controls than the
UPS. In a brownout, the UPS might go to its battery while the ATS would remain
connected to a low utility source because its critical setpoint had not been
reached. This also means the engine generators would never start. In the end
result the UPS would run out of battery backup and crash.
- There may also be interfaces with other building systems depending on the
circumstances or local building regulations. In some cases, you may wish to
signal all elevators to return to the ground floor in the event of a power
failure. In this case a pre-signal from the ATS could be interfaced with the elevator
controls for that purpose.
Power transfer switching can be complex, and the more you know the better.
There are many types of power switching mechanisms, platforms, and control
devices, which are right for you? Join me next issue for a look at closed
transition ATS.